Loading...
01-10048 1997 UPCc.111�daeda���a Published in the Salina Journal on JulyJ72001 ORDINANCE NUMBER 01-10048 AN ORDINANCE PROVIDING FOR THE AMENDMENT OF ARTICLE VI OF CHAPTER 8 OF THE SALINA CODE PERTAINING TO BUILDINGS BY ADOPTING THE 1997 UNIFORM PLUMBING CODE. BE IT ORDAINED by the Governing Body of the City of Salina, Kansas: Section 1. That Sections 8-176, 8-178, 8-179, 8-180, 8-181, 8-182, 8-183, 8-185, and 8-186 of Chapter 8 of the Salina Code are hereby amended to read as follows: "Sec. 8-176. Uniform Plumbing Code adopted. There is hereby adopted, by reference, by the city for the purpose of providing minimum standards to safeguard life or limb, health, property, and public welfare by regulating and controlling the design, construction, quality of materials, location, operation, alteration, repair, maintenance, of plumbing and drainage systems within the city and certain equipment specifically regulated therein, that certain plumbing code known as the Uniform Plumbing Code, recommended and published by the International Association of Plumbing and Mechanical Officials, being particularly the 1997 edition not including appendices thereto, except as amended in this article of the Salina Code, of which not fewer than three (3) copies have been, and are now filed in the office of the City Clerk and the same are hereby incorporated as fully as if set out at length herein and the provisions thereof shall be controlling in the construction of all buildings and structures therein contained within the corporate limits of the city. Sec. 8-178. Amendments to Chapter 1 - Administration of the Uniform Plumbing Code. 103.1.2.3 No permit shall be required to replace equivalent fixtures or traps which were initially installed with slip joint fittings. No permit shall be required for the replacement or installation of flexible gas appliance connectors. 103.4.1 Permit Fees. The fee for each permit shall be as set forth in the fee schedule adopted pursuant to section 2-2 of the Salina Code of Ordinances. 103.4.2 Deleted 103.4.3 Deleted. Sec. 8-179. Amendments to Chapter 2 - Definitions of the Uniform Plumbing Code. 205.0 (-C-) Certified Backflow Assembly Tester. A person who has shown competence to test and maintain backflow assemblies to the satisfaction of the Administrative Authority having jurisdiction. Cesspool. A lined excavation in the ground which receives the discharge of a drainage system or part thereof, so designed as to retain the organic matter and solids discharging therein, but permitting the liquids to seep through the bottom and sides. Chemical Waste. See Special Wastes. Clarifier. See Interceptor. Cleanout. In addition to typical definition, cleanout will include a fixture trap or a fixture with integral trap, readily removable without disturbing concealed piping shall be acceptable as a cleanout equivalent. Clear Water Waste. Cooling waster and condensate drainage from refrigeration and air conditioning equipment; cooled condensate from steam heating systems; cooled boiler blowdown water. Clinic Sink. A sink designed primarily to receive wastes from bedpans and having a flush rim, an integral trap with a visible trap seal, and the same flushing and cleansing characteristics as a water closet. Code. This publication: Uniform Plumbing Code.. Cc ll�tl, Id 51111 Combination Thermostatic/Pressure Balancing Valve. A mixing valve which senses outlet temperature and incoming hot and cold water pressure and compensates for fluctuations in incoming hot and cold water temperatures and pressures to stabilize outlet temperatures. Combination Waste and Vent System. A specially designed system of waste piping embodying the horizontal wet venting of one or more sinks or floor drains by means of a common waste and vent pipe, adequately sized to provide free movement of air above the flow line of the drain. Combined Building Sewer. See Building Serwer, (Combined). Combustible Construction. A structure in which any member of its structural framework will ignite and burn at a temperature of 1392°F (756°C) or less. Common. That part of a plumbing system which is so designed and installed as to serve more than one (1) appliance, fixture, building, or system. Conductor. A pipe inside the building which conveys storm water from the roof to a storm drain, combined building sewer, or other approved point of disposal. See Downspout. Confined Space. A room or space having a volume less than fifty (50) cubic feet per 1000 Btu/h (1.4 m3/293W) of the aggregate input rating of all fuel burning appliances installed in that space. Contamination. An impairment of the quality of the potable water which creates an actual hazard to the public health through poisoning or through the spread of disease by sewage, industrial fluids or waste. Also defined as High Hazard. Continuous Vent. A vertical vent that is a continuation of the drain to which it connects. Continuous Waste. A drain connecting the compartments of a set of fixtures to a trap or connecting other permitted fixtures to a common trap. Critical Level. The critical level C -L or C/L marking on a backflow prevention device or vacuum breaker is a point conforming to approved standards and established by the testing laboratory (usually stamped on the device by the manufacturer) which determines the minimum elevation above the flood level rim of the fixture or receptacle served at which the device may be installed. When a backflow prevention device does not bear a critical level marking, the bottom of the vacuum breaker, combination valve, or the bottom of any such approved device shall constitute the critical level. Cross -Connection. Any connection or arrangement, physical or otherwise, between a potable water supply system and any plumbing fixture or any tank, receptacle, equipment or device, through which it may be possible for non -potable, used, unclean, polluted and contaminated water, or other substances, to enter into any part of such potable water system under any condition. Sec. 8-180. Amendments to Chapter 3 - General Regulations of the Uniform Plumbing Code. 316.1.3 Soldered Joints. Joints in copper tubing shall be made by appropriate use of approved copper or copper alloy fittings. Surfaces to be joined by soldering shall be cleaned bright by manual or mechanical means. The joints shall be properly fluxed with an approved type flux, and made up with approved solder. Flux is not required to be water-soluble for water supply piping. All solder and fluxes shall be manufactured to approved standards. Solders and fluxes with a lead content which exceeds two-tenths (0.20) of one (1) percent are prohibited in piping systems used to convey potable water. 316.1.8 Copper Crimping System Joints. Joints formed using a copper crimping system are approved for use provided the system has been listed and tested. Manufacturer installation instructions and maintenance requirements for all equipment must be followed. 317.0 Increasers and Reducers. Where different sizes of pipes or pipes and fittings are to be connected, the proper size increasers or reducers or reducing fittings shall be used between the two sizes. The use of other types of fittings for the increasing or reducing of pipe sizes is approved provided the flow of material through the pipe is not diminished. Brass or cast iron body cleanouts shall not be used as a reducer or adapter from cast iron drainage pipe to iron pipe size (IPS) pipe. c ��m�aaieo-sE,�,e Sec. 8-181. Amendments to Chapter 4 -Plumbing Fixtures and Fixture Fittings of the Uniform Plumbing Code. 412.2 Location of Floor Drains. Floor drains shall be installed in the following areas: 412.2.1 Toilet rooms containing two (2) or more water closets or a combination of one (1) water closet and one (1) urinal, except in a dwelling unit. 412.2.2 Commercial kitchens. 412.2.3 Laundry rooms in commercial buildings and common laundry facilities in multi -family dwelling buildings when indirect waste or trough type drains are being used. 413.0 Minimum Number of Required Fixtures. (See Table A -29-A of the 1997 Uniform Building Code as adopted by the City of Salina.) 413.1 Fixture Count. Plumbing fixtures shall be provided for the type of building occupancy and in the minimum number shown in Table A -29-A of the 1997 Uniform Building Code as adopted by the City of Salina. 413.3 Separate Facilities. See Chapter 29 of the 1997 Uniform Building Code as adopted by the City of Salina for these requirements. Sec. 8-182. Amendments to Chapter 5 — Water Heaters of the Uniform Plumbing Code. 509.0 Prohibited Locations Water heaters which depend on the combustion of fuel for heat shall not be installed in a room used or designed to be used for sleeping purposes, bathroom, clothes closets or in a closet or other confined space opening into a bath or bedroom. Exception: Direct vent water heaters. Where not prohibited by other regulations, water heaters may be located under a stairway or landing. The replacement of fuel burning water heaters that are located in bathrooms or closets accessible from a bathroom shall be permitted. Sec. 8-183. Amendments to Chapter 6 — Water Supply and Distribution of the Uniform Plumbing Code. 603.3.2 The premise owner responsible person shall have the backflow prevention assembly tested by a certified backflow assembly tester at the time of installation, repair, or relocation and tested and overhauled on the schedule listed in Chapter 41 Division 4 Cross Connections. of the City of Salina Code of Ordinances. The periodic testing shall be performed in accordance with the procedures referenced in Table 14-1 by a tester qualified in accordance with those standards. 603.4.6.1 Potable water supplies systems having no pumps or connections for pumping equipment, and no chemical injection or provision for chemical injection, shall be protected from backflow by one of the following devices: 1. Atmospheric vacuum breaker 2. Pressure vacuum breaker 3. Reduced pressure backflow preventer 4. Double check valve assembly 603.4.6.4 Systems which include a chemical injector or have any provision for chemical injection designed to add chemicals to the potable water system shall be prohibited. 608.5 Relief valves located inside a building shall be provided with a drain, not smaller than the relief valve outlet, of galvanized steel, hard drawn copper piping and fittings, CPVC, or listed relief valve drain tube with fittings which will not reduce the internal boor of the pipe or tubing (straight lengths as opposed to coils) and shall extend from the valve to an indirect waste receptor if drainage piping is readily accessible or to within six inches of the floor and shall be pointed downward if drainage piping is not readily accessible. The discharge pipe shall be installed in a manner to minimize personal injury or property damage and so that draining water is readily observable by the building occupants. A pan may be utilized to prevent property damage. A pan installed for this purpose is not required to be drained. Such drains may terminate at other approved locations. No part of such drain pipe shall be trapped and the terminal end of the drain pipe shall not be threaded. saieai� oai+z 609.9.5 All new or repaired public or private water mains or plumbing lines serving more than one property shall be disinfected prior to use as required by the City of Salina Department of Utilities. 609.10 Water Hammer. All building water supplies systems in which quick acting valves over installed shall be provided with devices to absorb high pressures resulting from the quick closing of these valves. Quick closing valves are defined as valves operated by an electrical solenoid or a ball valve operated by a lever. Gate valves or wheel valves are not considered quick closing valves. These pressure absorbing devices shall be either air chambers or approved mechanical devices. Water pressure shock arresters shall be installed as close as possible to quick acting valves at the end of long pipe or near batteries of fixtures or both. Water pressure shock arresters or pressure absorbing devices are not required for residential structures with separate water services. Sec. 8-185. Amendments to Chapter 7 — Sanitary Drainage of the Uniform Plumbing Code. 710.9 All such pumps and receiving tanks shall be automatically discharge and, when in any public use occupancy with an occupant load of greater than 15 as determined by the 1997 Uniform Building Code as adopted by the City of Salina shall be provided with dual pumps or ejectors arranged to function independently in case of overload or mechanical failure. The lowest inlet shall have the minimum clearance of two (2) inches (51 mm) from the high water or "starting" level of the sump. When two pumps are required an alarm system approved by the Administrative Authority shall be installed. 710.14 With the approval of the Administrative Authority pumps other than sewage ejector pumps, sewage pumps or grinder pumps may be used to discharge sinks in single-family residences. 712.1 Media. The piping of the plumbing, drainage, and venting systems shall be tested with water or air. The Administrative Authority may require the removal of any cleanouts, etc., to ascertain if the pressure has reached all parts of the system. After the plumbing fixtures have been set and their traps filled with water, they shall be submitted to a final test. Exception: No testing will be required for plastic DWV systems. Sec. 8-186. Amendments to Chapter 8 — Indirect Wastes of the Uniform Plumbing Code. 807.4 Deleted." Section 2. That Sections 8-187 through 8-189 of Chapter 8 of the Salina Code is hereby added to read as follows: "See. 8-187. Amendments to Chapter 9 — Vents of the Uniform Plumbing Code. 906.8 Air Admittance Valves 906. 8.1 General. Vent systems utilizing air admittance valves shall comply with this section. Individual and branch type air admittance valves shall be listed and shall conform to AS SE 1051. 906.8.2 Installation. The valves shall be installed in accordance with the requirements of this section and manufactures installation instructions. Air admittance valves shall be installed after the DWV testing required by Section 712.2 or 712.3 has been performed. 906.8.3 Where permitted. In remodel construction where venting above the roof is impractical, individual and branch vents shall be permitted to terminate with a connection to an air admittance valve when first approved by the Administrative Authority. The air admittance valve shall only vent fixtures that are on the same floor level. 906.8.4 Location. The air admittance valve shall be located the minimum of six inches above the highest flood level rim of the fixture being served. The air admittance valve shall be located within the maximum developed length permitted for the vent. The air admittance valve shall be installed the minimum of six inches above insulation materials. 906.8.5 Access and Ventilation. Access shall be provided to all air admittance valves. The valve shall be located within a ventilated space that allows air to enter the valve. o,,,d S,1 906.8.6 Size. The air admittance valve shall be rated for the size of the vent to which the valve is connected. 908.0 Vertical Wet Venting 908.4 One horizontal offset may be permitted in a wet vented section. The length of the offset will be limited to the lengths of trap arms as required in table 10-1. Sec. 8-188. Amendments to Chapter 11— Storm Drainage of the Uniform Plumbing Code. 1101.0 General. This chapter has not been adopted but has been moved to the appendix. It will be used by the Administrative Authority for guidance and reference purposes. Sec. 8-189. Amendments to Chapter 13 — Medical Gas Systems of the Uniform Plumbing Code. 1301.0 Scope Plans for Medical Gas Systems shall be prepared by a mechanical engineer licensed by the State of Kansas. A written certification stating the plans are in compliance with this chapter must be provided. Inspection of medical gas systems will be done using the special inspection method outlined in Chapter 17 of the 1997 Uniform Building Code as adopted by the City of Salina. The engineer of record shall utilize an inspection program approved by the building official prior to issuance of the permit to install a medical gas system. The inspection program shall designate the portions of the work that require special inspection and the name or names of the individuals or firms who are to perform the special inspections, and indicate the duties of the special inspectors. The special inspector shall be employed by the owner, the engineer or architect of record, or an agent of the owner, but not the contractor or any other person responsible for the work." Section 3. That the existing Sections 8-176, 8-178, 8-179, 8-180, 8-181, 8-182, 8-183, 8-185, and 8-186 are hereby repealed Section 4. That this ordinance shall be in full force and effect August 1, 2001 from and after its adoption and publication once in the official city newspaper. {SEAL} ATTEST: Lieu Ann Nicola, City Clerk Introduced: July 16, 2001 Passed: July 23, 2001 jii�stiin M. �Seaon,